What this will do is link any message instruction in SLC_A that is pointed to node 1 to the IP address 192.168.1.200 which is the NET-ENI attached to SLC_B. So you need to configure node 1 with IP address “192.168.1.200” which is ENI_B.

Now, within ENI_A you have to have the node table configured with at least one node linked to the IP address of ENI_B. Attached to SLC_A is a NET-ENI (let’s call it ENI_A) with an IP address of 192.168.1.100 and attached to SLC_B is a NET-ENI (let’s call it ENI_B) with an IP address of 192.168.1.200. So, let’s label each SLC5/03, the first one will be SLC_A and the other SLC_B. You need/want at least one of the SLC5/03’s to communicate with the other SLC5/03.
Rslogix 500 msg instruction driver#
This appears to be working as you can see both SLC5/03’s in RSLinx (I’m assuming via an Ethernet driver in RSLinx). Each NET-ENI module has its own IP address which is what RSLinx is using to communicate with the SLC5/03’s. If I understand correctly you have two SLC5/03’s each with a NET-ENI connected to them via DF1 full duplex. I’m not really sure what you mean in your answer. So go ahead and set up separate areas of memory for your control block and your data payload and verify that you've configured the Net-ENI correctly on both sides, and let us know what you find. Can you describe in detail where that error message appears ? RSLogix 500 doesn't know anything about IP addresses when you're using an SLC-5/03 controller, and there are only three error codes the Net-ENI can generate, none of which are specific to IP addresses. I'm not sure why you would get a message that says "No IP Address Configured On Network". If this is the only MSG that's outgoing, you should be OK.Ĥ. Remember that the Net-ENI has only a small number of TCP connections it can handle two incoming, two outgoing, and two either way.
Rslogix 500 msg instruction manual#
You need to have configured the IP address of the target device equivalent to DF1 Node 0 in the Net-ENI utility or by using a configuration message inside the SLC-5/03.Ĭonfiguring the DF1:IP table is described in the 1761-UM006 user manual for the 1761-NET-ENI on page 4-6 and in Chapter 5.ģ. Sending an outgoing message via a 1761-NET-ENI requires you to use the DF1 Address : IP Address table inside the Net-ENI. I typically do not use the same data file for my Control Blocks as for the actual data payloads, and I use separate data files for data I'm transmitting and data I expect to receive.Ģ. Your actual data payload must use different memory addresses. If you are planning to use N7:0 as the start of your Control Block, you need to reserve N7:0 through N7:13.
Rslogix 500 msg instruction serial#
The Control Block for a MSG instruction that uses the SLC-5/03 serial port is 14 Words long. Other applications that use RSLinx can also access the programs as if they were on a communications network.This is an intermediate difficulty programming challenge. When RSLogix Emulate is running with programs in memory, you can use the Who Active or RSWho functions and see the emulator as if it was a PLC-5 on a Data Highway Plus network or an SLC-500 on a DH485 network.

When you have configured the driver, click OK. You can also type a name for RSLogix Emulate in the Station Name field. Remember, RSLogix Emulate is being treated as if it were a hardware device, so it needs a unique station number. Type a station number for RSLogix Emulate in the Station Number field. RSLinx displays a dialog for configuring the driver. RSLinx displays a dialog for naming the driver you selected.
Rslogix 500 msg instruction drivers#
RSLinx displays the Configure Drivers dialog.įrom the Available Driver Types list, select PLC-5 (DH+) Emulator or SLC-500 (DH485) Emulator, and click the Add New button. In RSLinx, click Communications > Configure Drivers.
Rslogix 500 msg instruction how to#
Here's how to set up communications between RSLinx and RSLogix Emulate:

Basically, you'll set up communications between RSLogix Emulate and RSLinx exactly as if RSLogix Emulate is a hardware device. If you have set up your communications for your physical processors, you'll find setting up communications for RSLogix Emulate a simple procedure.